| Caracteristică | Valoare |
|---|---|
| DECUPAJ mm | 24x24 |
| Notă | Due to dangerous overvoltage and overheating, the Current Transformator is not allowed to be operated with open secondary Side. (EN 60044-1 /A2) As soon as the Measurement Device, the Energy Counter or the Net Analyzer is disconnected, the secondary Side has to be shortcutted! |
| Curent primar | 50 A |
| Conexiune | ## |
| Metodă de montaj | Prin pini |
| Rated dynamic current Idyn | 2.5Ith |
| Accuracy classes | ## |
| Max. Operating voltage Um | 0.72kV r.m.s. |
| Short-time current Ith | < 60Ipr |
| Reference temperature | 23°C ±1°C °C |
| LxBxH mm | 35x46x65 |
| Unitate de ambalare | 1 m. |
| Carcasă | ## |
| disipare | 1,00 W |
| PREG | 2330 |
| Burden | Class 1 (1VA) |
| Accesorii opționale | MGF39000--;MGF37900--;MGX20006--;MGX20406-- |
| Thermal rated continuous current according to EN60044-1 | ## |
| Cablu de conexiune | lengh 100cm;Cross-section 14AWG / 2.08mm² |
| Gama de temperatură - Funcţionare | -15 to +50 °C |
| Working conditions | ## |
| COD COMANDĂ | MG922005 |
| Intended use | for cables up to diameter 24mm |
| Specifications | ## |
| Rated current secondary side Isr | 5A |
| Housing material | Polycarbonate, self-extinguishing |
| Winding primary side | Cable and busbar feedthrough |
| Masă netă | 0,24 kg/m |
| Rated frequency | 50-60Hz Hz |
| Temperatura maximă a mediului ambiant | 75 °C |
| Isolation | Class B (EN60044-1);Class E (EN60044-1) |
| Gama de temperatură - Transport/Depozitare | -25 to +75 °C |
| grad de protecţie | IP20 |
| Insulation requirements | ## |
| Temperatura minimă a mediului ambiant | -25 °C |
| Clasă | 1 |
| Categorie produs | Normal installation (DIN EN 61869-2) |
| Standard produs | EN 61869-2 |
| Rated current primary side Ipr | 50 A |
| Load current error | For class 1 and 5% In: ±3%.;For class 1 and 20% In: ±1.5%;For class 1 and 100% In: ±1%.;For class 1 and 120% In: ±1%;For class 1 and 150% In: ±1% |
| Decupaj mm | 24x24 mm |
| Diametru maxim conductor | 24 mm |
| Tip | Split-core transformers for cables |
| Isolation test voltage | 3 kV R.M.S. 50 Hz/1min |
| Masă g | 240 |
| Versiune | Dry type transformer, air insulation |